SERVICE MANUAL
OFFICE PRO 60
SERIAL NUMBER FROM APRIL 2007 (0407) TO PRESENT
DocID: 00G00016E
Vista de pagina 0
1 2 3 4 5 6 ... 68 69

Indice de contenidos

Pagina 1 - SERVICE MANUAL

SERVICE MANUALOFFICE PRO 60SERIAL NUMBER FROM APRIL 2007 (0407) TO PRESENTDocID: 00G00016E

Pagina 2

Operation Section103.3 Internal Structure3.4 Basic Construction• The MovinCool Office Pro 60 is compact in construction because the condenser and thee

Pagina 3 - Table of Contents

Operation Section113.5 Air Flow• Air drawn from the right side face passes through the condenser which extracts the heat. Thishot air is blown out thr

Pagina 4

Operation Section124. SPECIFICATIONS4.1 Technical SpecificationsITEM SPECIFICATIONScinortcelElenaP lortnoCserutaeF cinortcelEcinortcelElortnoC tatsom

Pagina 5

Operation Section13• Specifications are subject to change without notice.< NOTE >*1 :Rating Condition: 95 °F (35 °C), 60 %RH*2 :Measured at 3.28

Pagina 6 - 1. PRECAUTIONS FOR SAFETY

Operation Section144.2 Characteristics (at 230 V)I0019106560505545402030352515>evruC ecnereffiD erutarepmeT riA looC<>evruC yticapaC gnilooC&

Pagina 7 - 2. GENERAL DESCRIPTION

Operation Section154.3 Characteristics (at 208 V)I0019116560505545402535403020>evruC ecnereffiD erutarepmeT riA looC<>evruC yticapaC gnilooC&

Pagina 8 - 3. CONSTRUCTION

Operation Section165. REFRIGERANT SYSTEM5.1 Refrigerant System ConstructionThe component parts of the refrigerant system include the following:• Compr

Pagina 9 - 3.2 Exterior Components

Operation Section175.2 Compressor• The compressor used for the unit is hermetically sealed. The compressor and the compressormotor are in one casing.(

Pagina 10 - 3.4 Basic Construction

Operation Section185.3 Condenser• The condenser is a heat exchanger with copper tubes that are covered with thin aluminumprojections called plate fins

Pagina 11 - 3.8 Drain Tanks (optional)

Operation Section196. ELECTRICAL SYSTEM6.1 Circuit Diagram and Control BoxI001913TB2TB1GAC 208/230 V 1φ 60 HzAPGGGGT1TB13L21L1HIHILOLOMF22T15L3MCCMCCM

Pagina 12 - 4. SPECIFICATIONS

© 2008 DENSO SALES CALIFORNIA, INC.All rights reserved. This book may not be reproduced or copied, in whole or in part, without the written permission

Pagina 13 - < NOTE >

Operation Section206.2 Basic Operation of The Office Pro 60 Electrical Circuit• There are two basic components used to control the operation of the Of

Pagina 14 - Operation Section

Operation Section21(2) Cool mode• In addition to fan mode (as described above), when the COOL ON/OFF button on the controlpanel is pressed, the microp

Pagina 15

Operation Section226.3 Control Box(1) Capacitors• The capacitors are used to temporarily boost the power output available to the fan motor andthe comp

Pagina 16 - 5. REFRIGERANT SYSTEM

Operation Section23(2) Relay board• The relay board receives signals and outputsfrom the control board that contains amicroprocessor. The relay board

Pagina 17 - 5.2 Compressor

Operation Section246.4 Fan Motor(1) For evaporator• The fan motor is a single phase, induction typetwo-speed motor.Specifications:- Rated Voltage: 230

Pagina 18 - Gas and Liquid Mixture

Operation Section256.6 Condensate Pump• The Office Pro 60 is equipped with a condensate pump, which collects the water that forms onthe evaporator dur

Pagina 19 - 6. ELECTRICAL SYSTEM

Operation Section26- To insure proper drainage, locate the highestvertical position, no more than 17 ft (5.2 m) at230 VAC (13 ft (4 m) at 208 VAC), an

Pagina 20 - (1) Fan mode

Operation Section276.7 Drain Switch• The Office Pro 60 is equipped with a drain tank switch. When the drain tanks accumulatesapproximately 8.0 gal (30

Pagina 21 - (2) Cool mode

Operation Section28(1) How to re-start the unit• If the LCD indicates “PROGRAM ON”, press the COOL ON/OFF button to continue running theprogram. If th

Pagina 22 - 6.3 Control Box

Operation Section296.11 Fan Mode Control Switch• The fan motor operation is controlled by relays on the relay board through a microprocessor inthe con

Pagina 23 - (3) Relay board fuse

Table of ContentsTable of ContentsOperation Section1. PRECAUTIONS FOR SAFETY1.1 Foreword. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 24 - 6.5 Compressor Motor

Operation Section306.13 Warning Signal Connection (Output Signal Terminal L+ and L-)• The controller is equipped with a warning signal output relay ty

Pagina 25 - 6.6 Condensate Pump

Repair Section317. TROUBLESHOOTING7.1 Troubleshooting• Before troubleshooting the system, the following inspection should be performed.(1) Inspection

Pagina 26

Repair Section327.2 Self-Diagnostic Codes• Self-diagnostic codes are displayed on the control board under the following conditions andclear method is

Pagina 27 - 6.7 Drain Switch

Repair Section33Show LCD and LED all on modePress HI/LO and U buttons simultaneously for 3 sec. (To check LCD segments and LED display.)After 5 sec.,

Pagina 28 - 6.10 Temperature Control

Repair Section347.3 Troubleshooting Chart• To accurately troubleshoot the problem, it is important to carefully confirm the nature of theproblem. Typi

Pagina 29 - 6.11 Fan Mode Control Switch

Repair Section35SymptomPossible CauseRemedyChecking Area CauseAir volume normalCompressor operates.1. Usage conditions (high temperature).Operation ne

Pagina 30

Repair Section36(2) Unit does not start (operate)< NOTE >• In this case, there is a possibility of safety device activating due to the clogged a

Pagina 31 - 7. TROUBLESHOOTING

Repair Section37Control panel displayturns onControl Paneldisplay shows error codes.1. Display code “FL”. Drain tanks (optional) are filled with the d

Pagina 32 - 7.2 Self-Diagnostic Codes

Repair Section38(3) Overflow of drain waterSymptomPossible CauseRemedyChecking Area CauseStops immediately after startingControl panel display normall

Pagina 33

Repair Section39(4) Abnormal noise or vibration• To prevent abnormal noise or vibration, carefully determine the source of the problem and comeup with

Pagina 34 - 7.3 Troubleshooting Chart

Table of Contents6.3 Control Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 35

Repair Section40(3) Inspection of cooling capacity performance• Measure the difference in temperature between the inlet of the evaporator and the cool

Pagina 36

Repair Section418. DISASSEMBLY8.1 Parts ConstructionI001923EvaporatorFanCondensatePumpControl PanelAir Outlet GrillCondenser FanUpper PanelRear PanelP

Pagina 37

Repair Section428.2 Disassembly1) Remove drain tanks (optional).2) Remove twelve (12) screws from upper frontpanel.3) Slide upper front panel forward

Pagina 38 - (3) Overflow of drain water

Repair Section435) Remove nine (9) screws from service panel andthirteen (13) screws from rear left panel.6) Remove eight (8) screws from rear right p

Pagina 39 - 7.4 Basic Inspection

Repair Section449) Remove nine (9) screws from rear panel.10) Remove twelve (12) screws from front left panel.I001930Screws (9)I001931Screws (12)

Pagina 40 - Evaporator Air In

Repair Section458.3 Removal of Electrical Parts(1) Control box1) Remove nine (9) screws from service panel. (See page 43.)2) Remove electrical parts.-

Pagina 41 - 8. DISASSEMBLY

Repair Section46(2) Relay board1) Remove nine (9) screws from service panel. (See page 43.)2) Disconnect ten (10) connectors, and remove five (5) scre

Pagina 42 - 8.2 Disassembly

Repair Section473) Slowly slide control panel assembly out of box.4) Disconnect the following connectors from thecontrol board:(A) J201 (10-pin) Wire

Pagina 43 - Repair Section

Repair Section48(4) Battery replacement of control board• When the power is unplugged from the unit, and control board is automatically resetting cloc

Pagina 44 - Screws (12)

Repair Section498.4 Removal of Blower AssemblyI001932CondenserFan MotorCondenser Housing BoxEvaporator Fan CasingEvaporator FanCondenser FanCasingCond

Pagina 45 - (1) Control box

Table of ContentsRepair Section7. TROUBLESHOOTING7.1 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 46 - (3) Control board

Repair Section50(1) Removal of condenser fan and fan motor1) Loosen the set screw using a hex key.2) Remove six (6) nuts in the location shown.3) Remo

Pagina 47

Repair Section515) Turn the fan motor around and place on mountingbracket. Secure condenser fan motor with two (2)nuts.6) Remove six (6) screws from r

Pagina 48

Repair Section522) Remove evaporator fan motor wire and two (2)ties. Remove four (4) nuts from housing whileholding fan securely with one hand. Then r

Pagina 49

Repair Section538.6 Inspection of Capacitor (for Fan Motor and Compressor)(1) Ohmmeter method• Set the ohm-meter to the 10M range. Place thetwo probes

Pagina 50 - Ties (3)

Repair Section548.8 Inspection of Fan Motor(1) Condenser fan motor• Measure resistance across the terminals of thefan motor. (All terminals must be di

Pagina 51

Repair Section558.10 Inspection of Wiring Connection• Refer to the Wiring Diagrams on page 19 and check for connection of each wire.8.11 Inspection of

Pagina 52

Repair Section569. REFRIGERANT SYSTEM REPAIR9.1 Repair of Refrigerant System• In case there is a leak, obstruction, or trouble in the refrigerant sys

Pagina 53 - (2) Capacitance tester method

Repair Section57(4) Use of dry nitrogen gas• During brazing, the inside of the pipe undergoes an oxidative reaction due to the brazing flame.Introduce

Pagina 54 - 8.8 Inspection of Fan Motor

Repair Section589.2 Removal of Refrigeration Cycle ComponentsCAUTION• Before any refrigeration cycle component can be replaced, it is necessary to rec

Pagina 55 - 8.12 Inspection

Repair Section599.3 Charging the System with R-410A Refrigerant• Always ensure that the refrigerant system has been properly evacuated before charging

Pagina 56 - 9. REFRIGERANT SYSTEM REPAIR

Operation Section61. PRECAUTIONS FOR SAFETY1.1 Foreword• This manual has been published to service the MovinCool Office Pro 60. Please use this servic

Pagina 57 - (5) Vertical Joint

Repair Section60(1) Connection of gauge manifold1) Properly remove the crushed end of the pinch-offtube at the high pressure side and the lowpressure

Pagina 58

Repair Section61(3) Checking vacuum1) Leave the high pressure valve and the lowpressure valve of the gauge manifold closed forfive min or more, and co

Pagina 59

Repair Section62(4) Checking gas leak1) Remove the charging hose (green) from thevacuum pump, and connect the hose to therefrigerant cylinder (R-410A)

Pagina 60 - (2) Evacuation

Repair Section63(5) Evacuation (repeat)1) Close the valve of the refrigerant cylinder. Thenremove the charging hose (green) from therefrigerant cylind

Pagina 61 - (3) Checking vacuum

Repair Section649.4 Refrigerant Charging Work(1) Refrigerant charging1) Remove the charging hose (green) from thevacuum pump, and connect it to the re

Pagina 62 - (4) Checking gas leak

Repair Section65(2) Removal of gauge manifold1) Crimp the pinch-off tube with a pinch-off tool.2) Remove the gauge manifold and the processtube fittin

Pagina 63 - (5) Evacuation (repeat)

Repair Section6610. REASSEMBLY10.1 Removal of Unit• Reassemble the unit in the reverse order of removal. Described below are the parts that requirespe

Pagina 64 - 9.4 Refrigerant Charging Work

Repair Section6710.4 Wiring Notice• Secure the wires using clamps so that they do not come into contact with the edges of thestructure, etc. Secure th

Pagina 65 - (2) Removal of gauge manifold

Repair Section6810.7 SchematicI001948<Wiring Diagram>AC 208/230 V 1φ 60 HzAPGGGGT1TB13L21L1HIHILOLOMF22T15L3MCCMCCMCMDPCondensate PumpRTH THS DS

Pagina 66 - 10. REASSEMBLY

DENSO SALES CALIFORNIA, INC.Long Beach, CA 90810www.movincool.comP/N: SV0002- 02 Third Issue: December 2008

Pagina 67 - 10.6 Caster Maintenance

Operation Section72. GENERAL DESCRIPTION2.1 Spot Cooler• In general, conventional air conditioners coolthe entire enclosed environment. They act as“he

Pagina 68 - 10.7 Schematic

Operation Section83. CONSTRUCTION3.1 Exterior DimensionsI001906(40.8)(8.5)(2.6)(29.9)(3.6)(51.6)(Unit: inch)(30.2)(55.0)(DIA. 15.7)(62.2)(6.1)(65.0)(1

Pagina 69 - Long Beach, CA 90810

Operation Section93.2 Exterior ComponentsI001907Cold Air Outlet GrillEvaporator Air Inlet GrillCondenser Air Outlet DuctService PanelPower CordCondens